E1 for Mid-Home Water Heaters
E1 for Mid-Home Water Heaters

If your i12, SHLX or SH12 is throwing an E1 code

Updated over a week ago

This is a troubleshot for when your mid-home water heater (this includes the models: i12, SHLX, and SH12) is giving you an E1 error.

An E1 error is related to an issue involving your gas supply on your Mid Home Tankless Water Heater.

Please follow the steps below:

Correct Gas Type

First, verify that your water heater is the correct gas type. On the right or left side of the water heater, there is a plate that specifies LP for Liquid Propane or NG for Natural Gas. This should match the type of gas that is being supplied. If this matches, verify that your installer checked to make sure that the gas is at the correct pressure for your i12, SHLX, or SH12.

Gas Pressure

Using a manometer, check if you have enough gas pressure. For more instructions on how to read gas pressure, please check this link.

The gas pressure needs to be measured in water columns, for Liquid Propane it is 10-13 inches of water column, and for Natural Gas is 4-8 inches of water column. If pressure drops during use it will cause an E1 error code.

Gas Piping Size

Check if you have the correct gas piping size. We recommend a minimum of ½ black steel gas line. If using a flex steel gas line, it must be rated a minimum of 80,000 BTU and will be marked on the package. Please check this link for more details.

Regulator

Make sure your installer used a regulator capable of delivering the proper gas pressure needed for your water heater 80,000 BTU. Next, verify that your gas supply is turned on.

Gas Line Setup

How many elbows do you have in your gas line setup? Did you know that too many elbows can lower the pressure and cause issues with your gas?

Always refer to the user manual to make sure your installation is proper.

Propane Tank

If using LPG (Liquid Propane Gas) please ensure that your propane tank is not low or out of gas.

Obstruction of the Ventilation or Exhaust

Sometimes, unintentional debris will get into the exhaust on top of the unit and keep the system from correctly releasing and ventilating the fumes.

This will cause you to get an error code. You can check if this is the problem, by following the steps below:

  1. Remove the ventilation from the top of the unit.

  2. Look down into the exhaust on the top to see if anything has fallen into it: screws, sheetrock pieces during installation, etc.

  3. If it looks clear, try running the unit without the exhaust connected to the ventilation. It could be something clogging the ventilation that is not attached to the unit. (the piping leading outdoors).

  4. If the unit runs fine without being connected to the ventilation outside, then something is clogging your ventilation system. It's not the unit.


Contact Our Support

If after checking all of the above, you are still having problems with the E1 code, please contact your support by live chat or sending us an email at [email protected].

Please be advised that you will need to provide us with:

  • Pictures of your gas pressure at all 2 places in your gas setup while the water heater is not in use and while in use. We need readings from your manometer at the regulator and on the gas valve inside your water heater. Once more, here is the file on where to take the readings.

  • Pictures of your gas regulator with specs and your gas line setup all the way to your tankless water heater.